What are the regulations on oxygen pipelines for medical oxygen generators?

Release time: 2022-09-01

Oxygen pipelines are the key equipment for transporting oxygen. Because oxygen is a combustion gas, the following aspects should be paid attention to when laying medical oxygen generators:

1. The use of oxygen pipelines should be suitable for the flow of oxygen to be transported and the working pressure of oxygen.

2. There are three methods for oxygen pipelines: empty frame laying, pipe trench laying and buried laying. The connection of the oxygen pipeline should be welded by electric welding, and the connection between the pipeline and the machine equipment, gate valve, accessories, etc. can be connected by flanges or bolts. When bolting, lead monoxide, sodium silicate or tetrafluoroethylene plastic film should be used as fillers. It is forbidden to use hemp or cotton fiber coated with lead red, or other raw materials containing vegetable oil to prevent easy ignition when oxygen leaks. fuel.

3. The oxygen pipeline must be built on the support frame of the non-combustible body.

4. The oxygen pipeline is not suitable for crossing high temperature and fire areas. When necessary, heat insulation measures should be added to the pipeline. The wall thickness temperature should not exceed 700°C. Fire and oil stains are not allowed to approach the oxygen pipeline and gate valve.

5. The oxygen pipeline should be set up with a grounding system to eliminate static electricity.