An oxygen generator is a type of machine that produces oxygen. The principle is to use air separation technology to compress the air with high density and then use the different condensation points of each component in the air to separate the gas and liquid at a certain temperature. from further distillation. So what conditions need to be met for the use of industrial oxygen generators?
First, The oxygen generator meets the conditions
1. The inspectors in the production workshop of the industrial oxygen generator must strictly implement the shift system. At the end of the shift, they should carefully check the condition of all equipment and remaining problems, inform the repair personnel in time, and deal with safety hazards in time. After the problem is solved, then take over.
2. Before starting the industrial oxygen generator, it is necessary to check the equipment according to the rules of the comprehensive automatic work management system. After checking, inform the central control center to start or stop the industrial oxygen generator.
3. At work, it is necessary to strictly implement the rules of the industrial oxygen generator induction automation work management system, make specific and careful records, and deal with the problems found in a timely manner and report them to the centralized control center. Problems that cannot be handled should be reported to the control center in a timely manner and recorded at the same time.
4. Eliminate all illegal operations, carefully study business knowledge, and strive to achieve three understandings and four meetings. It is necessary to immediately inform the centralized control center to stop the processing of abnormal phenomena in the work of the industrial oxygen generator, and it is strictly forbidden to work dangerously with the equipment.
Second, What are the requirements of the oxygen generator for the oxygen pipeline?
Oxygen pipeline is an important facility for transporting oxygen. Since oxygen is a combustion-supporting gas, the following points should be paid attention to when laying the oxygen generator:
1. The selection of the oxygen pipeline should be suitable for the flow rate and pressure of the delivered oxygen.
2. The oxygen pipeline can be laid in three ways: overhead laying, trench laying and buried laying. The connection of the oxygen pipeline should be welded, and the connection between the pipeline and equipment, valves, accessories, etc. can be flanged or threaded. When threaded connection, lead monoxide, water glass or tetrafluoroethylene film should be used as filler. It is strictly forbidden to use hemp or cotton silk coated with lead red, or other grease-containing materials to avoid igniting combustibles when oxygen leaks.
3. The oxygen pipeline must be erected on the support of the non-combustible body.
4. The oxygen pipeline should not pass through the high temperature and flame area. When it must pass, heat insulation measures should be added to the pipe section. The temperature of the pipe wall should not exceed 700C. It is strictly forbidden to open fire and oil pollution near the oxygen pipeline and valve.
5. The oxygen pipeline should be equipped with a grounding device to remove static electricity.
The above are the operating conditions of the industrial oxygen concentrator? What are the requirements for the oxygen pipeline? All explanations, if you want to know more about the company, please consult the website customer service